| Water cooled
chillers cool by the circulation of water and refrigerant through
coaxial tubing. The innermost tube contains the refrigerant while
the surrounding outer tube contains the water. As the system circulates,
the water in the outer tube condenses the refrigerant in the inner
tube, the refrigerant then flows through the evaporator. This condensation
process cools the liquid in the evaporator. The cooled liquid flows
to the reservoir tank. The system is closed so less heat is dissipated
into ambient air. Water cooled chillers are quiet and reliable,
they are also energy efficient. Water cooled chillers require a
substantial water source and system of pumps, piping and fans.
As the system tonnage rises the merit of a water cooled chiller
increases. |
Water-Cooled
5 to 15 HP Specifications
Model
|
DCW500
|
DCW750 |
DCW1000 |
DCW1300 |
DCW1500 |
| Compressor |
Nom.
HP
|
5 |
7.5 |
10 |
13 |
15 |
| Cooling
Capacity (1) |
Tons
Watts
BTU/hr
|
5.07
17,825
60,840 |
6.90
24,260
82,800 |
10.32
36,284
123,840
|
12.80
45,004
153,600
|
15.66
55,060
187,920 |
| Nominal
Evaporator Flow (2) |
USGPM
|
12.7 |
17.0 |
25.7 |
31.7 |
38.6 |
| Pressure
(3) |
PSIG
|
34.5 |
32 |
42 |
38 |
33.5 |
| Pump
Horsepower |
HP
|
1 |
1 |
2 |
2 |
2 |
| Water
Condenser Flow-Tower Water |
USGPM
|
15.4 |
22.3 |
31.5 |
38.8 |
47.0 |
| Water
Condenser Connections |
Inches
|
1 |
1 |
1-1/2 |
2 |
2 |
| Process
Connections (to & from) |
Inches
|
1-1/2 |
1-1/2 |
1-1/2 |
2 |
2 |
| Resivoir
Tank Capacity |
US
Gallons
|
16 |
16 |
45 |
45 |
45 |
| Dimensions
(d x w x h) |
Inches
|
53
x 34.5 x 40 |
53
x 34.5 x 40 |
75
x 34.5 x 40 |
75
x 34.5 x 40 |
75
x 34.5 x 40 |
| Shipping
Weight |
Pounds
|
915 |
1,005 |
1,105 |
1,190 |
1,195 |
| Temperature
Range |
ºF
ºC
|
32ºF
- 86ºF
0ºC - 30ºC |
32ºF
- 86ºF
0ºC - 30ºC |
32ºF
- 86ºF
0ºC - 30ºC |
32ºF
- 86ºF
0ºC - 30ºC |
32ºF
- 86ºF
0ºC - 30ºC |
| Temperature
Stability |
ºF
ºC
|
± 2ºF
± 1.11ºC |
± 2ºF
± 1.11ºC |
± 2ºF
± 1.11ºC |
± 2ºF
± 1.11ºC |
± 2ºF
± 1.11ºC |
| Nominal
Rated Amps |
460V/3/60
|
12.3 |
16.5 |
22.8 |
32.0 |
33.1 |
230V/3/60
|
24.0 |
33.3 |
49.6 |
64.0 |
66.2 |
Notes:
(1) Capacity based on 95ºF (35ºC) entering air, and leaving water 50 ºF.
Allowance made for heat gain from pump.
(2) Chiller flow rate based on 2.4 USGPM/ton (0.54 cu. Meters/hr/ton).
(3) Pumps: Stainless Steel Centrifugal
|