Air cooled chillers cool by a fan blowing air over a condenser coil converting the refrigerant from a gas state to a liquid state. The refrigerant then runs through an evaporator cooling the liquid in the evaporator, that liquid then flows to the reservoir tank. The compressor pushes the refrigerant through the system. Air cooled chillers have a small footprint with a compact design. They do not require a water tower with associated water pumps, piping and fans, reducing installation and maintenance costs. Air cooled chillers are easy to install, just plug them into a power source and they are ready for use. These chillers are the standard for smaller facilities.

Air-Cooled 18 to 25 HP Specifications

Model
DCA1800
DCA2000
DCA2300
DCA2500
Compressor
Nom. HP
18 (2@9)
20 (2@10)
23 (10+13)
25 (12+13)
Cooling Capacity (1)
Tons
Watts
BTU/hr
16.11
56,642
193,320
18.24
64,131
218,880
20.58
77,422
246,940
22.80
80,235
273,600
Nominal Evaporator Flow (2)
USGPM
40.1
46.2
51.8
58.3
Pressure (3)
PSIG
46
55
5960
65
Pump Horsepower
HP
3
5
5
2 @ 2
Fan(s)
HP
2 @ 1.5
2 @ 2
2 @ 2
75.0
Condenser Discharge Air Flow
CFM
9,000
10,500
12,000
13,500
Process Connections (to & from)
Inches
2

2

2
2
Resivoir Tank Capacity
US Gallons
100
100
100
100
Dimensions (d x w x h)
Inches
97 x 44 x 91
97 x 44 x 91
97 x 44 x 91
97 x 44 x 91
Shipping Weight
Pounds
2,275
2,575
2,875
3,075
Temperature Range
ºF
ºC
32ºF - 86ºF
0ºC - 30ºC
32ºF - 86ºF
0ºC - 30ºC
32ºF - 86ºF
0ºC - 30ºC
32ºF - 86ºF
0ºC - 30ºC
Temperature Stability

ºF
ºC

± 2ºF
± 1.11ºC
± 2ºF
± 1.11ºC
± 2ºF
± 1.11ºC
± 2ºF
± 1.11ºC
Nominal Rated Amps
460V/3/60
45.0
48.3
55.0
60
230V/3/60
93.0
99.9
-
-

Notes:
(1) Capacity based on 95 ºF (35ºC) entering air, and leaving water 50 ºF. Allowance made for heat gain from pump.
(2) Chiller flow rate based on 2.4 USGPM/ton (0.54 cu. Meters/hr/ton).
(3) Pumps: Stainless Steel Centrifugal