| Air cooled chillers
cool by a fan blowing air over a condenser coil converting the
refrigerant from a gas state to a liquid state. The refrigerant
then runs through an evaporator cooling the liquid in the evaporator,
that liquid then flows to the reservoir tank. The compressor pushes
the refrigerant through the system. Air cooled chillers have a
small footprint with a compact design. They do not require a water
tower with associated water pumps, piping and fans, reducing installation
and maintenance costs. Air cooled chillers are easy to install,
just plug them into a power source and they are ready for use.
These chillers are the standard for smaller facilities. |
Air-Cooled
1.5 to 3 HP Specifications
Model |
DCA150 |
DCA200 |
DCA300 |
| Compressor |
Nom.
HP |
1.5 |
2 |
3 |
| Cooling
Capacity (1) |
Tons
Watts
BTU/hr
|
1.48
5,200
17,732
|
1.99
7,000
23,885
|
2.99
10,500
35,827
|
| Nominal
Evaporator Flow (2) |
USGPM |
3.72 |
4.82 |
6.92 |
| Pressure
(3) |
PSIG |
60 |
7.5 |
14 |
| Pump
Horsepower |
HP |
1/3 |
1/5 |
1/3 |
| Fan(s) |
HP |
1/6 |
2
@ 1/6 |
2 @ 1/6 |
| Condenser
Discharge Air Flow |
CFM |
1070 |
2470 |
2170 |
| Process
Connections (to & from) |
Inches |
1/2 |
3/4 |
3/4 |
| Resivoir
Tank Capacity |
US
Gallons |
7 |
7 |
7 |
| Dimensions
(d x w x h) |
Inches |
30
x 21 x 34 |
30.5
x 37 x 42 |
30.5
x 37 x 42 |
| Shipping
Weight |
Pounds |
360 |
570 |
580 |
| Temperature
Range |
ºF
ºC
|
41ºF
- 95ºF
5ºC - 35ºC
|
41ºF
- 95ºF
5ºC - 35ºC |
41ºF
- 95ºF
5ºC - 35ºC |
| Temperature
Stability |
ºF
ºC
|
±
0.9ºF
± 0.5ºC
|
± 0.9ºF
± 0.5ºC |
± 0.9ºF
± 0.5ºC |
| Nominal
Rated Amps |
460V/3/60 |
- |
8.5 |
13.3 |
230V/3/60 |
- |
14 |
20 |
230V/1/60 |
12 |
22 |
29 |
Notes:
(1) Capacity based on 68ºF (20ºC) entering air, and leaving water 68ºF.
Allowance made for heat gain from pump.
(2) Chiller flow rate based on 2.4 USGPM/ton (0.54 cu. Meters/hr/ton).
(3) Pumps: DCA150 - Positive Displacement; DCA200 and DCA300 - Magnetic
Drive Centrifugal.
|