| Water cooled chillers cool by the circulation of water and refrigerant
through coaxial tubing. The innermost tube contains the refrigerant
while the surrounding outer tube contains the water. As the system
circulates, the water in the outer tube condenses the refrigerant
in the inner tube, the refrigerant then flows through the evaporator.
This condensation process cools the liquid in the evaporator. The
cooled liquid flows to the reservoir tank. The system is closed so
less heat is dissipated into ambient air. Water cooled chillers are
quiet and reliable, they are also energy efficient. Water cooled
chillers require a substantial water source and system of pumps,
piping and fans. As the system tonnage rises the merit of a water
cooled chiller increases. |
Water-Cooled
18 to 25 HP Specifications
Model
|
DCW1800
|
DCW2000 |
DCW2300 |
DCW2500 |
| Compressor |
Nom.
HP
|
18
(2@9) |
20
(2@10) |
23
(10+13) |
25
(12+13) |
| Cooling
Capacity (1) |
Tons
Watts
BTU/hr
|
17.45
61,353
209,400 |
19.70
69,264
236,400 |
22.60
79,530
271,200 |
24.50
86,217
294,000 |
| Nominal
Evaporator Flow (2) |
USGPM
|
43.3 |
49.7 |
56.6 |
62.6 |
| Pressure
(3) |
PSIG
|
45 |
53.5 |
59 |
63.5 |
| Pump
Horsepower |
HP
|
3 |
5 |
5 |
7.5 |
| Water
Condenser Flow-Tower Water |
USGPM
|
53.2 |
61.0 |
69.0 |
75.0 |
| Water
Condenser Connections |
Inches
|
2 |
2 |
2 |
2 |
| Process
Connections (to & from) |
Inches
|
2 |
|
2 |
2 |
| Resivoir
Tank Capacity |
US
Gallons
|
100 |
100 |
100 |
100 |
| Dimensions
(d x w x h) |
Inches
|
97
x 44 x 48 |
97
x 44 x 48 |
97
x 44 x 48 |
97
x 44 x 48 |
| Shipping
Weight |
Pounds
|
1,810 |
1,815 |
1,965 |
2,015 |
| Temperature
Range |
ºF
ºC
|
32ºF
- 86ºF
0ºC - 30ºC |
32ºF
- 86ºF
0ºC - 30ºC |
32ºF
- 86ºF
0ºC - 30ºC |
32ºF
- 86ºF
0ºC - 30ºC |
| Temperature
Stability |
ºF
ºC
|
± 2ºF
± 1.11ºC |
± 2ºF
± 1.11ºC |
± 2ºF
± 1.11ºC |
± 2ºF
± 1.11ºC |
| Nominal
Rated Amps |
460V/3/60
|
41.0 |
43.9 |
51.0 |
55.0 |
230V/3/60
|
82.0 |
90.7 |
- |
- |
Notes:
(1) Capacity based on 95ºF (35ºC) entering air, and leaving water 50 ºF.
Allowance made for heat gain from pump.
(2) Chiller flow rate based on 2.4 USGPM/ton (0.54 cu. Meters/hr/ton).
(3) Pumps: Stainless Steel Centrifugal
|